Precautions For Installation Of Electric Two-Way Ball Valve
Leave a message
1. The actuator can be installed at any angle, but the actuator must be above the level of the valve body.
2. Do not use force on the drive during installation. Otherwise the drive will be damaged.
3. The thread connected to the valve must be a standard international pipe thread (i.e. G thread). Do not use tapered threads to connect to the valve.
Door connection.
4. Before installation, valves and pipes should be kept clean and free of debris.
5. Valves and pipes should be installed horizontally or vertically, but must not be inverted.
6. When removing the valve body and installing it, never exert force on the valve stem, otherwise the valve stem will deform and cause failure.
7. Ordinary ball valves cannot be equipped with three-speed switches. They can only be equipped with mechanical or electronic thermostats and three-wire and one-control drives.
ball valve, various thermostats are available.
8. During debugging, it is necessary to observe whether the driver can start or stop reliably. If the ball continues to rotate, it must be adjusted.
Replace the driver, otherwise the seal life will be shortened.
9. Please ensure that the pipes and valves are insulated, and the actuator must not be wrapped in the insulation layer.